XDU

XDU Buddy

Vertiv coolant distribution unit diagnostics
V1.1

Start with the XDU symptom

Diagnose the secondary coolant loop, facility-water side, redundant pumps, valve, filtration, make-up system, leak detection, sensors and group controls without mixing liquid-cooling logic into a CRAC refrigeration diagnosis.

PROBLEM TO DIAGNOSE

Choose the closest symptom. Type the exact alarm on the next screen if one is active.

XDU CONFIGURATION

Model defaults will load automatically.
Safety: XDU/CDU equipment contains hazardous voltage, rotating pumps and pressurized liquid. Isolate electrical power and both liquid circuits, verify zero pressure and use the specified coolant/PPE before opening filters, pumps, valves or piping. A controller OFF command does not isolate power.
Fast path: Select the problem and model, then enter only known controller or field readings. Relevant loop sections open automatically.

CONTROLLER AND PUMP STATUS

Type the A-code, full wording, or both. Matching uses the selected model family.
Primary finding

Complete the conditions first

Secondary ΔT—
Secondary ΔP—
HX Approach—

WHAT SHOULD BE HAPPENING

    MOST LIKELY CAUSES

      DIAGNOSTIC ORDER

            Field reminder: Do not condemn a pump, control board or heat exchanger until the alarm code, model family, pump mode, valve position, facility-water condition, isolation valves, filter differential pressure, air removal and independent sensor readings are verified.